Add to Favorites
Share

Cooper RVAC Ring Main Unit Electrical Switchgear Distributors

  • Description
Product Detail

    Cooper RVAC Ring Main unit Cabinet

    1. Structural Characteristics

    All-weather, strong adaptability to environment

    l  Pass water-immersion test under 12kV power in 24 hours, protection level is IP68,  reliably withstand summer flooding.

    l  SF6  gas box is made of stainless steel plate and the surface is painted with antirust paint to prevent the influence of salt water, moisture, contamination and temperature so that it can keep durable and beautiful appearance.

    l  Equipped with COOPER prefabricated shielded touchable cable accessories, it can be plugged and unplugged with power and it can operate underwater or other harsh conditions for a long time.

    Fully sealed, fully insulated, maintenance-free

    l  All the high-voltage energized parts are enclosed in the main cabinet which can’t be reached.

    SF6 gas box Zero gauge pressure can withstand up to 32KV (1min), it has large insulation margin.

    Load switch cabinet (k unit/k1 unit)

    Load switch cabinet

    Load switch fuse combination cabinet (T unit)

    Load switch fuse combination cabinet

    CB cabinet (V unit)

    CB cabinet

    Metering cabinet (M unit)/PT cabinet (PT unit)

     Metering cabinet

    2. Main Parameters

    Items

    Unit

    Load Switch

    Fuse Combination

    Vacuum Circuit Breaker

    Rated voltage

    kV

    12

    12

    12

    Rated current

    A

    630

    125*

    630

    Power frequency withstand voltage (1min)

    Interphase, to-ground, between breaks

    kV

    42

    48

    42

    48

    42

    48

    Lightning impulse withstand voltage (BlL)

    Interphase, to-ground, between breaks

     

    kV

    75

    85

    75

    85

    75

    85

    Zero indication (1min) power frequency withstand voltage

    kV

    32

    32

    32

    Secondary circuit power frequency withstand voltage (1min)

    V

    2000

    2000

    2000

    Rated load breaking current

    A

    630

    630

    630

    Rated cable charging breaking current

    A

    10

    10

    25

    Rated short-circuit breaking current

    kA


    31.5*

    20

    Rated transfer breaking current

    A


    1700


    Rated short-circuit closed current (peak)

    kA/

    50/5


    50

    Grounding switch closed current (twice)

    kA/

    50/2


    50/2

    Rated short-time withstand current

    kA/s

    20/4

    20/4

    20/3

    Rated peak withstand current

    kA

    50

    50

    50

    Mechanical service life


    5,000

    5,000

    10,000

    SF6 gas rated pressure (20?)

    MPa

    0.03

    0.03

    0.03

    SF6 gas annual leakage rate

    %

    <0.05

    <0.05

    <0.05

    Note:

    RVAC is E3-class load switch, which meets not only GB3804, GB1984, GB3906, DL/T593 and other related GB standards, but also American ANSIC37.72 standard. 

    * It depends on the high-voltage fuse.


Send your message to this supplier